DKYS Series flow-controlled water softening systems measure the quantity of water passing through by means of a meter on the unit and subject it to a pre-programmed backwash process.
- Corrosion-resistant FRP (filament-wound) vessel
- Programmable automatic valve
- Time-controlled automatic backwash
- 3–6 bar operating pressure
Overview
Advantages
- Prevents scale formation.
- Increases the energy efficiency of heating systems.
- Extends the service life of boilers, heat exchangers and piping.
- Reduces soap and detergent consumption.
- Reduces maintenance and repair costs.
- Improves product quality in industrial processes.
- Maintains the performance of water-using equipment.
SYSTEM FEATURES
- Corrosion-resistant FRP (filament-wound) vessel
- Programmable automatic valve
- Time-controlled automatic backwash
- 3–6 bar operating pressure
- Maximum 10 bar test pressure
- Maximum operating temperature of 50 °C
- Ion exchange resin compliant with food regulations
- Brine tank
- 220 V / 50 Hz power supply
Areas of Use
- Houses and villas
- Hotels and Hospitality Facilities
- Hospitals
- Industrial production facilities
- Boiler feed water systems
- Cooling towers
- Laundries
- Food and beverage production facilities
- Car wash facilities
- Agricultural enterprises
Technical data
Standard models. Every project is sized from your water analysis.
DKYS MODELS TECHNICAL SPECIFICATIONS17 rows
| Model | SERVICE FLOW RATE (m³/h) | PRESSURE DROP (bar) | SERVICE (inch) | DRAIN (inch) | DIMENSIONS (cm) | RESIN (L) | BRINE TANK (L) | |||
|---|---|---|---|---|---|---|---|---|---|---|
| 20 m³/h | 30 m³/h | LA | LB | D | ||||||
| DKYS 30 | 1.5 | 2 | 0.2 | 3/4 | 1/2 | 104 | 89 | 25 | 30 | 70 |
| DKYS 50 | 1.5 | 2 | 0.2 | 3/4 | 1/2 | 153 | 137 | 25 | 50 | 70 |
| DKYS 60 | 2.2 | 3 | 0.2 | 3/4 | 1/2 | 148 | 132 | 30 | 60 | 70 |
| DKYS 80 | 2.5 | 3.5 | 0.2 | 1 | 1/2 | 153 | 137 | 33 | 80 | 100 |
| DKYS 100 | 3 | 4 | 0.2 | 1 | 1/2 | 181 | 165 | 36 | 100 | 100 |
| DKYS 150 | 4 | -- | 0.2 | 1 | 1/2 | 181 | 165 | 41 | 150 | 140 |
| DKYS 150 | 4 | 5.5 | 0.2 | 1 | 1/2 | 181 | 165 | 41 | 150 | 140 |
| DKYS 200 | 5.1 | 6.5 | 0.3 | 1 | 1/2 | 181 | 165 | 46 | 200 | 200 |
| DKYS 150 | 4 | 5.5 | 0.2 | 2 | 1 | 187 | 165 | 41 | 150 | 140 |
| DKYS 200 | 5.1 | 6.5 | 0.3 | 2 | 1 | 187 | 165 | 46 | 200 | 200 |
| DKYS 250 | 6.6 | 9 | 0.5 | 2 | 1 | 182 | 152 | 53 | 250 | 300 |
| DKYS 300 | 9 | 10 | 0.5 | 2 | 1 | 235 | 183 | 61 | 300 | 300 |
| DKYS 500 | 10 | ---- | 0.7 | 2 | 1 | 235 | 183 | 76 | 500 | 500 |
| DKYS 750 | 12 | ---- | 0.7 | 2 | 1 | 235 | 183 | 92 | 750 | 750 |
| DKYS 500 | 14 | 15 | 0.7 | 2 | 2 | 235 | 183 | 92 | 500 | 500 |
| DKYS 750 | 18 | -- | 0.7 | 2 | 2 | 235 | 183 | 92 | 750 | 750 |
| DKYS 900 | 20 | -- | 0.7 | 2 | 2 | 247 | 183 | 105 | 900 | 1000 |
Reference projects
Reference projects using this system
5-star hotel filtration and softening
5,000m³/daySand filter, activated carbon, softening
Laundry plant softening
3,000m³/daySoftening system
Water softening
More in water softening

ZKYS Series Water Softening System
With ZKYS Series time-controlled water softening systems, calcium and magnesium ions in the water are removed by the ion exchange principle.
- Corrosion-resistant FRP (filament-wound) vessel
- Programmable automatic valve

TYS Series Water Softening System
TYS Series duplex water softening systems are equipped with fully automatic control systems and consist of two softening units. The system can be…
- Twin-tank, corrosion-resistant FRP (filament-wound) vessel
- Programmable automatic valve

ETYS Series Water Softening System
With ETYS Frontal-Piped Single, Duplex and Triplex water softening systems, calcium and magnesium ions in the water are removed by the ion exchange…
- Cationic resin, maximum operating pressure 6 bar
- Octopus diffuser bottom collector structure
Request a quote
Ready to talk about your water?
Capacity and source water are enough to start. A full analysis lets our engineers choose the right membranes and pre-treatment.