Most buildings, camps and industrial sites in the UAE store water in tanks: drinking water from the network or a desalination plant, process water, irrigation water or fire water. Sectional tanks built from bolted panels are a common choice because they can be carried into basements and onto rooftops and assembled where they stand. The two main families are steel tanks and GRP tanks. This article compares them on the points that matter in the UAE climate: heat, coatings, hygiene, assembly and maintenance.
What each type is
A GRP tank is built from glass-reinforced plastic panels, a composite of glass fibre and resin moulded into square panels that are bolted together with sealant at the joints. GRP does not rust, and the panels are light to handle.
A steel tank is built from pressed steel panels. Three types are common: hot-dip galvanised carbon steel, carbon steel with a coating or lining, and stainless steel, usually grade 304 or 316L. Carbon steel depends on its coating for corrosion protection. Stainless steel resists corrosion through the metal itself, with 316L used where the stored water or the surroundings are more corrosive.
Heat and sunlight
Tanks on UAE rooftops and in open yards sit in strong sun and high air temperatures for much of the year. Heat affects the stored water in any tank: warm water favours bacterial growth and can make drinking water less pleasant. The material changes how the tank responds.
- GRP has low thermal conductivity, so the panels slow the transfer of heat into the water. Outdoor GRP panels need resin and surface layers that resist UV light, and they should be opaque so that light does not reach the water and encourage algae.
- Steel conducts heat well, so an exposed steel tank warms with the sun unless it is insulated or shaded. Steel itself is not affected by UV light, although the coating on carbon steel can be.
- For both, insulation, shading, a sensible location and a turnover that keeps the water moving help keep temperatures down.
Coatings and corrosion
Corrosion is the main difference between the materials. Coastal air, humidity and chlorinated water are hard on bare carbon steel. Galvanised and coated steel tanks rely on an intact protective layer: scratches during assembly, damage at bolt holes or wear over time expose the steel underneath, which then needs repair. Internal linings in contact with drinking water must be suitable for that use.
Stainless steel needs no coating, but the grade must suit the water. Water with a high chloride content, or a strongly chlorinated supply, can attack lower grades, which is why 316L is chosen for more demanding duties. Fasteners and any welds should match the panel grade so that no weak point is left.
GRP does not corrode. Its long-term performance depends instead on the quality of the resin, the surface finish and the protection against UV light on outdoor installations.
Hygiene and drinking water
For drinking water, the materials in contact with the water must be approved for potable use under the requirements that apply to the project. Beyond the material, hygiene comes from the design: smooth internal surfaces that are easy to clean, no light inside the tank, sealed covers and manholes, screened vents and overflows, and a layout without dead zones where water stands still.
GRP and stainless steel tanks can both meet these needs when they are specified and built correctly. Coated carbon steel can too, as long as the lining stays intact.
Assembly and site access
GRP and steel sectional tanks are both assembled on site from flat panels, so they pass through doors and stairwells where a one-piece tank cannot. GRP panels are lighter to carry. Steel panels are heavier but give a stiff structure that suits taller tanks. Both need a level base, usually a concrete plinth or steel beams designed for the full weight of the water, and both depend on correct sealing at the joints. Planning the base for the final size also leaves room to extend the tank later.
Maintenance over the life of the tank
- Every drinking water tank needs periodic inspection, cleaning and disinfection; the frequency is set by the operator and the applicable requirements.
- Bolts, seals and gaskets should be checked on all sectional tanks, because joints are where leaks start.
- Galvanised and coated steel tanks need checks for coating damage and corrosion, with repairs where the coating has failed.
- Stainless steel tanks need little beyond cleaning, but stained or damaged areas should be treated before they spread.
- Outdoor GRP tanks should be checked for surface wear from sunlight; indoor GRP tanks mainly need cleaning and joint checks.
How to choose
There is no single answer. The choice depends on what is stored, where the tank stands, its size and height, the site access, the client's specification and how the tank will be maintained. As a general guide:
- Drinking water inside a building, where light panels make installation easier: GRP and stainless steel are both common.
- Process water, warmer water or a specification that calls for a metal tank: stainless steel, with the grade matched to the water.
- Outdoor tanks in direct sun: either material, with UV-resistant GRP panels or an insulated steel tank.
- Coastal or corrosive locations: GRP or a suitable stainless steel grade rather than coated carbon steel.
AFG sectional water tanks
AFG manufactures GRP and stainless steel water tanks, the stainless range in 304 or 316L, as bolted sectional tanks that are built on site and can be extended by adding panels. The modular water tank page in the catalogue lists the design details. Tanks are often part of a larger water system, storing the product water of a reverse osmosis plant or a seawater desalination plant. Send the volume, the space available, the stored water and the location through the quote form and AFG will propose a material and panel layout.
FAQ